Liebert iCOM Microprocessor TM-10098 Manuel d'utilisateur Page 13

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 170
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 12
iCOM
Controls Training and Service Manual
The temperature controller deactivates the second stage of cooling (lag
compressor) when the return air temperature decreases to 50% of the cooling
proportional control band value. The first cooling stage (lead compressor) is
deactivated when the return air temperature decreases to the temperature set
point value or 0% of the cooling proportional control band value.
2 Stage Compressorized Cooling – No Dead Band
Temp Set Point: 70°F
Proportional Band: 8°F
70 71 72 73 74 75
Increasin
Temperature
Cool 1 On
Cool 1 Off
Cool 2 On
Cool 2 Off
Temp Set Point + (1/2 Proportional Band)
Note: in the above example that the control band begins at the 70°F temperature
set point and has a length of 4°F, which is ½ of the programmed temperature
proportional band value.
As the return air temperature increases Cooling 1 (lead compressor) is activated at
72°F or 50% of the cooling control band. If the return air temperature continues to
increase Cooling 2 (lag compressor) will activate at 74°F or 100% of the cooling
control band.
When the return air temperature starts to decrease, Cooling 2 (lag compressor) is
deactivated at 72°F or 50% of the cooling control band and Cooling 1 (lead
compressor) is deactivated at the temperature set point of 70°F or 0% of the
cooling control band.
12
Vue de la page 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 169 170

Commentaires sur ces manuels

Pas de commentaire