CSU3000 Chiller Designed For Siemens Magnetom Harmony/Symphony 1
Keeping Business in Business
CSU3000 Chiller Designed
For Siemens Magnetom Harmony/Symphony
Dedicated, equipment-matched cooling supplies the proper temperature and water flow, year round.
Factory-tested, piped, wired, and charged for hassle-free start-up and operation.
Local service and parts for quick and knowledgeable maintenance and service
Optional switch-over to alternate water source provides redundant continuous operation.
Optional remote monitoring systems keep you informed of chiller operation.
Standard product ETL/CSA Certified.
ISO 9000 Certified Company.
Magnetom Harmony/Symphony Specifications
Fluid Specified Water/Glycol
Max Heat Dissipation—BTUH (kW) 102,390
Fluid Temperature Range—°F (°C) 43-54 (6-12)
Fluid Flow Rate—GPM (l/m) 13 (50)
Fluid Pressure Drop—PSI (kPa) 21.8 (150)
Process Fluid Chiller Specifications
Model Number CS135A
Fluid Circulated Water
Net Cooling Capacity—BTUH (kW) 116,000 (34)
Leaving Fluid Temperature—°F (°C) 45 (7.2)
Fluid Flow Rate—GPM (l/m) 24 (91)
Harmony/ Symphony Pressure Drop—PSI (kPa) 21.8 (150)
Chiller Pressure Drop—PSI (kPa) 11.7 (81)
Pump Total Head—PSI (kPa) 56.3 (388)
Pump HP (kW) 3 (2.2)
Vue de la page 0
1 2

Résumé du contenu

Page 1 - CSU3000 Chiller Designed

CSU3000 Chiller Designed For Siemens Magnetom Harmony/Symphony 1Keeping Business in BusinessCSU3000 Chiller DesignedFor Siemens Magnetom Harm

Page 2 - Required Special Options

CSU3000 Chiller Designed For Siemens Magnetom Harmony/Symphony 21050 Dearborn DriveP.O. Box 29186Columbus, OH 43229Phone: 800.877.9222Fax: 61

Commentaires sur ces manuels

Pas de commentaire