Liebert Challenger ITR Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Climatiseurs à système divisé Liebert Challenger ITR. Liebert Challenger ITR User's Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 64
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Precision Cooling
For Business-Critical Continuity™
Liebert
®
Challenger
ITR
Installation Manual - Nominal Capacities 23 or 33 kW, 50 & 60Hz
Vue de la page 0
1 2 3 4 5 6 ... 63 64

Résumé du contenu

Page 1 - Challenger

Precision CoolingFor Business-Critical Continuity™Liebert® Challenger™ ITRInstallation Manual - Nominal Capacities 23 or 33 kW, 50 & 60Hz

Page 2 -

Installation4Figure 2 Cabinet dimensionsDPN001523Pg. 2, Rev. 1Filter Accessby Opening DoorUNITTOP VIEW32-1/2"(826mm)5/8"(16mm)9-5/8"(24

Page 3 - TABLE OF CONTENTS

Installation5Figure 3 Optional floor stand dimensions30-1/2"(775mm)30-1/2"(775mm)1"(25.4mm)See Specification Sheetfor height of floor s

Page 4

Installation62.5 Piping ConsiderationsConsideration should be given before installing refrigerant and liquid lines next to, under or above electronic

Page 5

Installation7Figure 4 Piping connections for air-cooled unitsPiping outlet locations through theplenum are the same as the unit.See below for descript

Page 6

Installation8Figure 5 Piping connections for split system fan coil unitsPiping outlet locations through theplenum are the same as the unit.See below f

Page 7 - 1.0 INTRODUCTION

Installation9Figure 6 Piping connections for water/glycol and GLYCOOL unitsPiping outlet locations through theplenum are the same as the unit.See belo

Page 8 - 2.0 INSTALLATION

Installation10Figure 7 Piping connections for chilled water self-contained unitsPiping outlet locations throughthe plenum are the same as theunit. See

Page 9 - 2.4.2 Removal of Skid

Installation112.6 Electrical ConnectionsThree-phase electrical service is required for all models in either 208, 230, 460, or 575 V, 60 Hz; or 200, 23

Page 10 - Figure 2 Cabinet dimensions

Installation129. Special alarm connections. Field-supplied 24V Class 1 wiring for special alarm. Connection made by adding normally open contacts betw

Page 11 - SL-11897

Installation132.8 Checklist for Completed Installation___ 1. Unpack and check received material.___ 2. Proper clearance for service access has been ma

Page 13 - Installation

Air-Cooled Models143.0 AIR-COOLED MODELS3.1 Condenser LocationThe air-cooled condenser should be located for maximum security and maintenance accessib

Page 14

Air-Cooled Models15Figure 9 Air-cooled condensersTable 3 Air-cooled condenser statisticsModel Numberof Fans Connection Sizes(OD Copper)Net Weightlb (k

Page 15

Air-Cooled Models163.3 Refrigerant PipingAll refrigeration piping should be installed with high temperature brazed joints. Prevailing good refrigerati

Page 16

Air-Cooled Models173.4 Fan Speed Control SystemsFan Speed Control provides an infinite number of speed variations on specially designed, permanent spl

Page 17 - 2.6 Electrical Connections

Air-Cooled Models183.4.2 Dehydration/Leak Test and Charging Procedures for R22 (standard) or R407C (Optional)Fan Speed Control Type CondenserDehydrati

Page 18 - 2.7.2 Plenum Installation

Air-Cooled Models19Figure 10 Air-cooled fan speed control general arrangementSL -11 89 7 PG 5 Con de nser Co il Sc hra d e r Va lv e Fu si bl e Pl

Page 19

Air-Cooled Models203.4.3 Charging1. Make sure unit is OFF. Open all disconnect switches and, on units supplied with circuit breakers, open all breaker

Page 20 - 3.0 AIR-COOLED MODELS

Air-Cooled Models213.5.2 Materials Supplied1. Built-in pre-wired condenser control box2. Air-cooled condenser3. Piping access cover to be reinstalled

Page 21

Air-Cooled Models22Dehydration/Leak Test1. Make sure unit is OFF. Open all disconnect switches and pull all fuses except control fuses. On units suppl

Page 22 - 3.3 Refrigerant Piping

Air-Cooled Models23Figure 11 Air-cooled, Lee-Temp general arrangementFACTORY PIPINGFIELD PIPINGSINGLE CIRCUIT SHOWNSL-10061 PG 4 SL-10071 PG 4Pipi

Page 23 - 3.4 Fan Speed Control Systems

iTABLE OF CONTENTS1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 24 - Dehydration/Leak Test

Water-Cooled Models244.0 WATER-COOLED MODELS4.1 Piping ConsiderationsManual shut-off valves should be installed at the supply and return lines of each

Page 25 - Air-Cooled Models

Water-Cooled Models25Figure 12 Water-cooled general arrangementSL-11898 PG 5EvaporatorCoilExpansionValveSensingBulbExternalEqualizersHot GasBypassValv

Page 26 - 3.5.1 Piping

Water-Cooled Models264.3 Water Regulating ValveThe water regulating valve automatically regulates the amount of fluid necessary to remove the heat fro

Page 27 - 3.5.2 Materials Supplied

Glycol/GLYCOOL-Cooled Models275.0 GLYCOL/GLYCOOL-COOLED MODELS5.1 Drycooler LocationThe drycooler should be located for maximum security and maintenan

Page 28 - 3.5.4 Charging

Glycol/GLYCOOL-Cooled Models285.4 Glycol PipingNOTICEGalvanized pipe must not be used in or with systems or units that contain glycol. The phosphates

Page 29 - SINGLE CIRCUIT SHOWN

Glycol/GLYCOOL-Cooled Models295.5 Filling Instructions5.5.1 Preparing the System for FillingIt is important to remove any dirt, oil or metal filings t

Page 30 - 4.0 WATER-COOLED MODELS

Glycol/GLYCOOL-Cooled Models305.5.2 Glycol SolutionsWhen considering the use of any glycol products in a particular application, you should review the

Page 31 - Water-Cooled Models

Glycol/GLYCOOL-Cooled Models315.5.3 Filling the SystemInstallation of hose bibs at the lowest point of the system is recommended. When filling a glyco

Page 32 - 4.3 Water Regulating Valve

Glycol/GLYCOOL-Cooled Models32Figure 14 Drycoolers and pump packages Notes1. Single pump packages are 17-1/4" (438 mm) wide. Dual pump packages a

Page 33 - 5.3 Electrical Connections

Glycol/GLYCOOL-Cooled Models33Figure 15 Pump packages—expansion tankTable 15 Mounting hole dimensional dataPUMP PACKAGE Ain (mm) Bin (mm)Cin (mm)SINGL

Page 34 - 5.4 Glycol Piping

ii5.2 Drycooler Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275.3 Ele

Page 35 - 5.5 Filling Instructions

Glycol/GLYCOOL-Cooled Models34Figure 16 Glycol general arrangementSL-11898 PG 6Glyco lPumpPumpHousingUnions*IsolationValves*ExpansionValveDrycoolerEle

Page 36 - 5.5.2 Glycol Solutions

Glycol/GLYCOOL-Cooled Models35Figure 17 GLYCOOL general arrangementSL-11901 PG 5PumpHousingGlyco lPumpUnions*IsolationValves*ExpansionValveEvaporatorC

Page 37 - 5.5.3 Filling the System

Glycol/GLYCOOL-Cooled Models365.6 CondenserThe condenser is designed to operate in conjunction with a drycooler. The maximum coolant pressure is 350 p

Page 38

Chilled Water Models376.0 CHILLED WATER MODELS6.1 Piping ConsiderationsManual shut-off valves should be installed at the supply and return lines to ea

Page 39 - SL-10065 PG 7B SL-10070 PG 6B

Split System Models387.0 SPLIT SYSTEM MODELSThree (3) condensing unit styles are available: two (2) air-cooled and one (1) water/glycol-cooled con-den

Page 40 - Glycol/GLYCOOL-Cooled Models

Split System Models397.3 Piping Considerations7.3.1 Refrigerant LoopAll split systems require two refrigerant lines (an insulated copper suction line

Page 41

Split System Models40Once all piping is complete, check for leaks and dehydrate the field piping as follows:1. Pressurize the field piping to 150 PSIG

Page 42 - 5.7 Glycol Regulating Valve

Split System Models41Figure 19 Refrigerant piping diagramTable 23 Equivalent lengths (feet) for various pipe fittingsCopper PipeOD in.90 DegreeElbow C

Page 43 - 6.0 CHILLED WATER MODELS

Split System Models427.3.2 Quick Connect FittingsBe especially careful when connecting the quick connect fittings. Read through the following steps be

Page 44 - 7.0 SPLIT SYSTEM MODELS

Split System Models437.4 Outdoor Air-Cooled Condensing UnitsFigure 20 Outdoor air-cooled condensing unit—horizontal air discharge modelsABCINDICATES A

Page 45 - 7.3 Piping Considerations

iiiFIGURESFigure 1 Removing Liebert Challenger ITR from skid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3F

Page 46

Split System Models44Table 24 Horizontal air discharge cabinet and floor planning dimensional dataModel Numbers Dimensional Data in. (mm) Module Weigh

Page 47 - Evaporator Condensing

Split System Models45Figure 21 Outdoor air-cooled condensing unit—top air discharge modelsSL-11081PG 5CA2"BLEFTAIRINTAKE(51mm)DGUARDHEIGHTTOPAIRD

Page 48 - 7.3.2 Quick Connect Fittings

Split System Models46Table 26 Cabinet and floor planning dimensional data - prop fan condensing modules, top air dischargeModel Numbers Dimensional Da

Page 49 - (See Table 24)

Split System Models47Figure 22 Electrical field connections, prop fan condensing moduleNOTE: Refer to specification sheet for full load amp

Page 50

Split System Models487.5 Centrifugal Air-Cooled Condensing Units7.5.1 Installing the Indoor Condensing UnitRefer to drawings for unit dimensions and c

Page 51 - DIMENSIONS

Split System Models49Figure 23 Detail of ceiling hanging bracket7.5.2 DuctingThe total external static pressure for the inlet and outlet ducts, includ

Page 52

Split System Models50Figure 24 Centrifugal air-cooled condensing unit dimensional dataSL-11087 PG 451 13/16 "1 3/4 "21 1/4 "1 5/8 "

Page 53 - SL-11081PG 8A

Split System Models51Figure 25 Centrifugal air-cooled condensing unit dimensional data (con't.)DPN000226Rev. 0Field-supplied unit disconnectswitc

Page 54

Split System Models52Figure 26 Split systems general arrangementSL-11900 PG 5CondenserCoil1/2" (12.7mm) NPTPressure Relief ValveSightGlassCheckVa

Page 55 - 7.5.2 Ducting

Split System Models537.6 Water and Glycol-Cooled Condensing UnitsFor installation guidelines, refer to Installing the Indoor Condensing Unit on page 4

Page 56 - SL-11087 PG 4

ivTABLESTable 1 Unit shipping weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 57

Split System Models54Figure 27 Water/glycol-cooled condensing unit dimensionsSL-11087PG 632 "32 "29 13/16 "33 5/8 "24 "(812.8

Page 58 - GLYCOL COOLED

Split System Models55Figure 28 Water/glycol-cooled condensing unit (con't.)DPN000228_Rev0Heat rejection connection.Field-supplied 24V NECClass 2

Page 59 - 7.6.4 Glycol Systems

R407C Refrigerant568.0 R407C REFRIGERANTTable 32 R407C pressure/temperature chart for operation and superheat (discharge/hot gas and suction gas)Tempe

Page 60 - SL-11087PG 6

R407C Refrigerant578.1 Calculating SubcoolingExampleMeasure the liquid pressure (e.g., 200 psig). Find the liquid saturation temperature at that press

Page 61 - DPN000228_Rev0

Ensuring The High AvailabilityOf Mission-Critical Data And Applications.Emerson Network Power, the global leader in enabling business-criticalcontinui

Page 62 - 8.0 R407C REFRIGERANT

Introduction11.0 INTRODUCTION1.1 System DescriptionsLiebert Challenger ITR™ environmental control systems are available in three main system configu-r

Page 63 - 8.1 Calculating Subcooling

Installation22.0 INSTALLATION2.1 Room PreparationThe room should be well insulated and must have a sealed vapor barrier. The vapor barrier in the ceil

Page 64 - SL-11956_REV0_07-08

Installation32.4.1 Handling With Skid• Always keep the Liebert Challenger ITR upright, indoors and protected from damage.• Do not use the extended rea

Commentaires sur ces manuels

Pas de commentaire