Precision CoolingFor Business-Critical Continuity™Liebert® Challenger™ ITRInstallation Manual - Nominal Capacities 23 or 33 kW, 50 & 60Hz
Installation4Figure 2 Cabinet dimensionsDPN001523Pg. 2, Rev. 1Filter Accessby Opening DoorUNITTOP VIEW32-1/2"(826mm)5/8"(16mm)9-5/8"(24
Installation5Figure 3 Optional floor stand dimensions30-1/2"(775mm)30-1/2"(775mm)1"(25.4mm)See Specification Sheetfor height of floor s
Installation62.5 Piping ConsiderationsConsideration should be given before installing refrigerant and liquid lines next to, under or above electronic
Installation7Figure 4 Piping connections for air-cooled unitsPiping outlet locations through theplenum are the same as the unit.See below for descript
Installation8Figure 5 Piping connections for split system fan coil unitsPiping outlet locations through theplenum are the same as the unit.See below f
Installation9Figure 6 Piping connections for water/glycol and GLYCOOL unitsPiping outlet locations through theplenum are the same as the unit.See belo
Installation10Figure 7 Piping connections for chilled water self-contained unitsPiping outlet locations throughthe plenum are the same as theunit. See
Installation112.6 Electrical ConnectionsThree-phase electrical service is required for all models in either 208, 230, 460, or 575 V, 60 Hz; or 200, 23
Installation129. Special alarm connections. Field-supplied 24V Class 1 wiring for special alarm. Connection made by adding normally open contacts betw
Installation132.8 Checklist for Completed Installation___ 1. Unpack and check received material.___ 2. Proper clearance for service access has been ma
Air-Cooled Models143.0 AIR-COOLED MODELS3.1 Condenser LocationThe air-cooled condenser should be located for maximum security and maintenance accessib
Air-Cooled Models15Figure 9 Air-cooled condensersTable 3 Air-cooled condenser statisticsModel Numberof Fans Connection Sizes(OD Copper)Net Weightlb (k
Air-Cooled Models163.3 Refrigerant PipingAll refrigeration piping should be installed with high temperature brazed joints. Prevailing good refrigerati
Air-Cooled Models173.4 Fan Speed Control SystemsFan Speed Control provides an infinite number of speed variations on specially designed, permanent spl
Air-Cooled Models183.4.2 Dehydration/Leak Test and Charging Procedures for R22 (standard) or R407C (Optional)Fan Speed Control Type CondenserDehydrati
Air-Cooled Models19Figure 10 Air-cooled fan speed control general arrangementSL -11 89 7 PG 5 Con de nser Co il Sc hra d e r Va lv e Fu si bl e Pl
Air-Cooled Models203.4.3 Charging1. Make sure unit is OFF. Open all disconnect switches and, on units supplied with circuit breakers, open all breaker
Air-Cooled Models213.5.2 Materials Supplied1. Built-in pre-wired condenser control box2. Air-cooled condenser3. Piping access cover to be reinstalled
Air-Cooled Models22Dehydration/Leak Test1. Make sure unit is OFF. Open all disconnect switches and pull all fuses except control fuses. On units suppl
Air-Cooled Models23Figure 11 Air-cooled, Lee-Temp general arrangementFACTORY PIPINGFIELD PIPINGSINGLE CIRCUIT SHOWNSL-10061 PG 4 SL-10071 PG 4Pipi
iTABLE OF CONTENTS1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Water-Cooled Models244.0 WATER-COOLED MODELS4.1 Piping ConsiderationsManual shut-off valves should be installed at the supply and return lines of each
Water-Cooled Models25Figure 12 Water-cooled general arrangementSL-11898 PG 5EvaporatorCoilExpansionValveSensingBulbExternalEqualizersHot GasBypassValv
Water-Cooled Models264.3 Water Regulating ValveThe water regulating valve automatically regulates the amount of fluid necessary to remove the heat fro
Glycol/GLYCOOL-Cooled Models275.0 GLYCOL/GLYCOOL-COOLED MODELS5.1 Drycooler LocationThe drycooler should be located for maximum security and maintenan
Glycol/GLYCOOL-Cooled Models285.4 Glycol PipingNOTICEGalvanized pipe must not be used in or with systems or units that contain glycol. The phosphates
Glycol/GLYCOOL-Cooled Models295.5 Filling Instructions5.5.1 Preparing the System for FillingIt is important to remove any dirt, oil or metal filings t
Glycol/GLYCOOL-Cooled Models305.5.2 Glycol SolutionsWhen considering the use of any glycol products in a particular application, you should review the
Glycol/GLYCOOL-Cooled Models315.5.3 Filling the SystemInstallation of hose bibs at the lowest point of the system is recommended. When filling a glyco
Glycol/GLYCOOL-Cooled Models32Figure 14 Drycoolers and pump packages Notes1. Single pump packages are 17-1/4" (438 mm) wide. Dual pump packages a
Glycol/GLYCOOL-Cooled Models33Figure 15 Pump packages—expansion tankTable 15 Mounting hole dimensional dataPUMP PACKAGE Ain (mm) Bin (mm)Cin (mm)SINGL
ii5.2 Drycooler Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275.3 Ele
Glycol/GLYCOOL-Cooled Models34Figure 16 Glycol general arrangementSL-11898 PG 6Glyco lPumpPumpHousingUnions*IsolationValves*ExpansionValveDrycoolerEle
Glycol/GLYCOOL-Cooled Models35Figure 17 GLYCOOL general arrangementSL-11901 PG 5PumpHousingGlyco lPumpUnions*IsolationValves*ExpansionValveEvaporatorC
Glycol/GLYCOOL-Cooled Models365.6 CondenserThe condenser is designed to operate in conjunction with a drycooler. The maximum coolant pressure is 350 p
Chilled Water Models376.0 CHILLED WATER MODELS6.1 Piping ConsiderationsManual shut-off valves should be installed at the supply and return lines to ea
Split System Models387.0 SPLIT SYSTEM MODELSThree (3) condensing unit styles are available: two (2) air-cooled and one (1) water/glycol-cooled con-den
Split System Models397.3 Piping Considerations7.3.1 Refrigerant LoopAll split systems require two refrigerant lines (an insulated copper suction line
Split System Models40Once all piping is complete, check for leaks and dehydrate the field piping as follows:1. Pressurize the field piping to 150 PSIG
Split System Models41Figure 19 Refrigerant piping diagramTable 23 Equivalent lengths (feet) for various pipe fittingsCopper PipeOD in.90 DegreeElbow C
Split System Models427.3.2 Quick Connect FittingsBe especially careful when connecting the quick connect fittings. Read through the following steps be
Split System Models437.4 Outdoor Air-Cooled Condensing UnitsFigure 20 Outdoor air-cooled condensing unit—horizontal air discharge modelsABCINDICATES A
iiiFIGURESFigure 1 Removing Liebert Challenger ITR from skid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3F
Split System Models44Table 24 Horizontal air discharge cabinet and floor planning dimensional dataModel Numbers Dimensional Data in. (mm) Module Weigh
Split System Models45Figure 21 Outdoor air-cooled condensing unit—top air discharge modelsSL-11081PG 5CA2"BLEFTAIRINTAKE(51mm)DGUARDHEIGHTTOPAIRD
Split System Models46Table 26 Cabinet and floor planning dimensional data - prop fan condensing modules, top air dischargeModel Numbers Dimensional Da
Split System Models47Figure 22 Electrical field connections, prop fan condensing moduleNOTE: Refer to specification sheet for full load amp
Split System Models487.5 Centrifugal Air-Cooled Condensing Units7.5.1 Installing the Indoor Condensing UnitRefer to drawings for unit dimensions and c
Split System Models49Figure 23 Detail of ceiling hanging bracket7.5.2 DuctingThe total external static pressure for the inlet and outlet ducts, includ
Split System Models50Figure 24 Centrifugal air-cooled condensing unit dimensional dataSL-11087 PG 451 13/16 "1 3/4 "21 1/4 "1 5/8 "
Split System Models51Figure 25 Centrifugal air-cooled condensing unit dimensional data (con't.)DPN000226Rev. 0Field-supplied unit disconnectswitc
Split System Models52Figure 26 Split systems general arrangementSL-11900 PG 5CondenserCoil1/2" (12.7mm) NPTPressure Relief ValveSightGlassCheckVa
Split System Models537.6 Water and Glycol-Cooled Condensing UnitsFor installation guidelines, refer to Installing the Indoor Condensing Unit on page 4
ivTABLESTable 1 Unit shipping weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Split System Models54Figure 27 Water/glycol-cooled condensing unit dimensionsSL-11087PG 632 "32 "29 13/16 "33 5/8 "24 "(812.8
Split System Models55Figure 28 Water/glycol-cooled condensing unit (con't.)DPN000228_Rev0Heat rejection connection.Field-supplied 24V NECClass 2
R407C Refrigerant568.0 R407C REFRIGERANTTable 32 R407C pressure/temperature chart for operation and superheat (discharge/hot gas and suction gas)Tempe
R407C Refrigerant578.1 Calculating SubcoolingExampleMeasure the liquid pressure (e.g., 200 psig). Find the liquid saturation temperature at that press
Ensuring The High AvailabilityOf Mission-Critical Data And Applications.Emerson Network Power, the global leader in enabling business-criticalcontinui
Introduction11.0 INTRODUCTION1.1 System DescriptionsLiebert Challenger ITR™ environmental control systems are available in three main system configu-r
Installation22.0 INSTALLATION2.1 Room PreparationThe room should be well insulated and must have a sealed vapor barrier. The vapor barrier in the ceil
Installation32.4.1 Handling With Skid• Always keep the Liebert Challenger ITR upright, indoors and protected from damage.• Do not use the extended rea